Water Blocked P6 or P6/P13 BFOU 3.6/6kV
Applications
-
These cables are partially water blocked, fire resistant, flame retardant, low smoke, halogen free and mud resistant, used for fixed installation for medium voltage power.
Standards
-
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004 VG 95218 part 29
Construction
-
l Conductors: Circular tinned annealed stranded copper to IEC 60228 class 2.
l Conductor Screen: Semi conducting material.
l Insulation: Mica tape + Halogen free EPR.
l Insulation Screen: Semi conducting material and tinned copper wire braid.
l Filler: Water blocking fillers, if required.
l Bedding: Halogen free compound, PETP wrapping tape will be applied over the bedding, if required.
l Armour: Tinned copper wire braid, PETP wrapping tape will be applied over the braiding, if required.
l Water Blocking Elements: Water blocking tape and strings for providing longitudinal water tightness.
l Inner Sheath: Halogen free thermosetting compound, SHF2 (for TYPE P6), or halogen free mud resistant thermosetting compound, SHF MUD (for TYPE P6/P13), coloured red.
l Outer Sheath: Polyurethane for providing transversal water tightness, PE is optional,but can not meet low smoke standard.
Electrical Characteristics
-
Nominal Cross Section Area mm² 25 35 50 70 95 120 150 Nominal Conductor Diameter mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1 Maximum DC Resistant@20℃ Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126 Continuous Current Rating@45℃1 Core A 127 157 196 242 293 339 389 Continuous Current Rating@45℃3 Core A 89 110 137 169 205 237 272 Short Circuit Current 1s A 3580 5010 7150 10020 13590 17170 21460 Operating Voltage KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
-
Nominal Cross Section Area mm² 185 240 300 400 500 630 Nominal Conductor Diameter mm 17.0 19.6 21.9 24.5 27.5 32.3 Maximum DC Resistant@20℃ Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286 Continuous Current Rating@45℃1 Core A 444 522 601 690 780 890 Continuous Current Rating@45℃3 Core A 311 365 421 483 546 623 Short Circuit Current 1s A 26470 34340 42930 57230 71540 90140 Operating Voltage KV 3.6/6 3.6/6 3.6/6 8.7/15 8.7/15 8.7/15
Ambient Temperature Correction Factors
-
Ambient Temperature Correction Factors 35 40 45 50 55 60 65 70 75 80 Rating Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Mechanical and Thermal Properties
- Bending Radius :15×OD (during installation); 9×OD (fixed installed).
- Temperature Range : -20℃ ~ +90℃.
Dimensions and Weight
Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm |
Nominal Bedding Thickness mm |
Nominal Inner Sheath Thickness mm |
Nominal Outer Sheath Thickness mm |
Nominal Overall Diameter mm |
|
Nominal Weight kg/km |
||||||
1×16 | 2.5 | 1.5 | 1.2 | 1 | 26.8±2 | 998 |
1×25 | 2.5 | 1.6 | 1.2 | 1.2 | 28.7±2 | 1166 |
1×35 | 2.5 | 1.6 | 1.2 | 1.2 | 30.0±2 | 1323 |
1×50 | 2.5 | 1.7 | 1.3 | 1.2 | 31.5±2 | 1533 |
1×70 | 2.5 | 1.7 | 1.3 | 1.2 | 33.3±2 | 1827 |
1×95 | 2.5 | 1.8 | 1.4 | 1.4 | 36.0±2 | 2216 |
1×120 | 2.5 | 1.9 | 1.4 | 1.4 | 37.7±2 | 2552 |
1×150 | 2.5 | 1.9 | 1.4 | 1.4 | 39.7±2 | 3035 |
1×185 | 2.5 | 2 | 1.5 | 1.4 | 41.9±2 | 3539 |
1×240 | 2.6 | 2.1 | 1.6 | 1.6 | 45.4±2 | 4305 |
1×300 | 2.8 | 2.2 | 1.6 | 1.6 | 47.9±2 | 5051 |
1×400 | 3 | 2.3 | 1.7 | 1.6 | 51.3±2 | 6101 |
1×500 | 3.2 | 2.5 | 1.8 | 1.6 | 55.3±2 | 7382 |
1×630 | 3.2 | 2.6 | 1.9 | 1.6 | 59.7±2 | 9062 |
3×16 | 2.5 | 2.3 | 1.7 | 1 | 49.8±2 | 3728 |
3×25 | 2.5 | 2.5 | 1.8 | 1.2 | 53.9±2 | 4389 |
3×35 | 2.5 | 2.6 | 1.9 | 1.2 | 57.1±2 | 5061 |
3×50 | 2.5 | 2.7 | 1.9 | 1.2 | 59.8±2 | 5765 |
3×70 | 2.5 | 2.8 | 2 | 1.2 | 64.0±2 | 6920 |
3×95 | 2.5 | 3 | 2.1 | 1.4 | 69.0±2 | 8316 |
3×120 | 2.5 | 3.1 | 2.2 | 1.4 | 72.9±2 | 9608 |
3×150 | 2.5 | 3.3 | 2.3 | 1.4 | 76.8±2 | 10983 |
3×185 | 2.5 | 3.4 | 2.4 | 1.4 | 81.4±2 | 12611 |
3×240 | 2.6 | 3.7 | 2.6 | 1.6 | 89.5±2 | 15425 |
3×300 | 2.8 | 3.9 | 2.8 | 1.6 | 95.1±2 | 17987 |